Knkong Electric Co.,Ltd

Knkong Electric Co.,Ltd

Manufacturer from China
Active Member
5 Years
Home / Products / Gas Insulated Switchgear /

Indoor SF6 MV Gis Switchgear 1250A 11kv Ring Main Unit

Contact Now
Knkong Electric Co.,Ltd
City:zhengzhou
Province/State:henan
Country/Region:china
Contact Person:MrKen Chan (English)
Contact Now

Indoor SF6 MV Gis Switchgear 1250A 11kv Ring Main Unit

Ask Latest Price
Video Channel
Brand Name :KNKONG
Model Number :HXGN15
Certification :CB,ISO
Place of Origin :China
MOQ :1
Supply Ability :50 units/Month
Delivery Time :12
type :11kv Ring Main Unit
name :SF6 switchgear
model :HXGN15
standard :CB,ISO
Voltage :12 24 36KV
Current :630,1250A
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description
GIS Insulated SF6 ring main unit switchgear 11kv Ring Main Unit
Indoor switchgear
SF6 Metal-Clad Enclosed Ring Main Unit
12 24 36KV50/60Hz, 630,1250A
OEM & ODM,Complete equipment
Meet IEC standards
Send us your SLD (Single Line Drawing) or requirements ,we design switchgear plan for you

Product Introduction

General

HXGN15 series unit type SF6 ring net cabinet with SF6 load switch as main switch, for whole cabinet is suitable for electric distribution automation and compact also expandable metal close switchgear. It characters in its simple structure, flexible operation, reliable interlocking and convenient installation etc., which can provide the satisfactory technical projects both for different application occasions and users. With the adoption of sensor technology and the protection relay up to date, plus the advanced technology and flexible assembly project, HXGN15 unit type SF6 ring net cabinet can completely meet the requirement of continuously variable market. It can take self-produced FLBS36 SF6 load break switch ; also according to user’s demand can be assembled with the internationally top-ranking VB4 series vacuum circuit breaker with permanent magnetic mechanism made by AREVA or HD4 type SF6 circuit breaker made by AREVA or HD4 type SF6 circuit breaker made by ABB or with our VS1-12 type vacuum circuit breaker with permanent magnetic mechanism. Operational methods for the main switch inside ring main unit can be either manual or electric power driven. And It can meet the requirement of Four Controls” when matched with FTU and RTU.

Feature
1. Metal-clad and fully enclosed structure, can prevent dirt and small animals from entrance.
2. Through the observation windows in the door panel, switch position and general condition can be clearly viewed.
3. The door and switch operating handle are mechanically interlocked to ensure the door cannot be opened with the switch closed and the switch cannot be closed with the door open.
4. The switchgear use vacuum switches combined with solid insulation material. This environmentally-friendly technology avoid the uses of SF6 as an insulation gas.
5. Reliable FIVE-PREVENTION interlock can effectively prevent from mal-operation.

Service Environment
1. Air temperature: -35℃~+40℃
2. Humidity: Monthly average humidity 95%; Daily average humidity 90% .
3. Altitude2500m
4. Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
5. No frequent violent shake

Technical Date

No. Item Unit Parameter
1 Rated voltage kV 12 24 36
2 Rated frequency Hz 50/60
3 Rated current A 630(1250*)
4

1min Power frequency

withstand voltage

wet kV 38 50 70
dry kV 48 60 85
5 Lightning impulse withstand voltage kV 75 125/150 170
6 Rated short circuit breaking current (peak) kA 80 63 63
7 Rated active load and close circuit breaking current A 63 50 50
8 Rated transferring current A 1700 1200 1200
9 Rated short circuit making current (peak) kA 80 63 63
10 Rated cable(line) charging breaking current A

50 and 10

50/10

11 Cable charge breaking current in earthing fault A 20 20 20
12 Rated withstand current (peak) kA 80 63 63
13 Short time withstand current (2s) kA 25 20 20
14 Mechanism life times 5000 2000 2000

Note: For short circuit breaking and peak current is based on Fuse plus combination