Knkong Electric Co.,Ltd

Knkong Electric Co.,Ltd

Manufacturer from China
Active Member
5 Years
Home / Products / Gas Insulated Switchgear /

IEC Fully Insulated 36KV 1250A RMU SF6 GIS Switchgear

Contact Now
Knkong Electric Co.,Ltd
City:zhengzhou
Province/State:henan
Country/Region:china
Contact Person:MrKen Chan (English)
Contact Now

IEC Fully Insulated 36KV 1250A RMU SF6 GIS Switchgear

Ask Latest Price
Video Channel
Brand Name :Knkong
Model Number :SF6 GIS HXGN-40.5
Certification :IEC ISO GB
Place of Origin :China
MOQ :1
Payment Terms :L/C, T/T
Supply Ability :100 Unit per month
Delivery Time :30 days
Packaging Details :Standard export packaging
Rating Voltage :36KV
Rating Current :Max 1250A
Rating Frequency :50/60Hz
Standards :GB ISO IEC
OEM/ODM :Please your CDA drawings
Type :Fully insulated
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Fully insulated HXGN-40.5kv SF6 RMU GIS GB ISO IEC Max 1250A

GB ISO 36KV Gas Fully Insulated Switchgear Medium Voltage Ring Main Unit

Product Introduction

General

The cable switch so-called C-unit is equipped with a double-position load switch and an independent earthing switch.
The load switch uses SF6 as its arc extinguishing medium, when the load switch at open position it meets the corresponding
requirements of the isolation switch.

Service environment

  • Air temperature: -35℃~+40℃
  • Humidity: Monthly average 95%; Daily average 90%.
  • Altitude:≤ 1000m (Up to 5000 m can be custom)
  • Ambient air not apparently polluted by corrosive and flammable gas, vapor, etc.
  • No frequent violent shake

Technical Data

No. Item Unit Parameter
1 Rated voltage kV 12 24 36
2 Rated frequency Hz 50/60
3 Rated current A 630(1250*)
4

1min Power frequency

withstand voltage

wet kV 38 50 70
dry kV 48 60 85
5 Lightning impulse withstand voltage kV 75 125/150 170
6 Rated short circuit breaking current (peak) kA 80 63 63
7 Rated active load and close circuit breaking current A 63 50 50
8 Rated transferring current A 1700 1200 1200
9 Rated short circuit making a current (peak) kA 80 63 63
10 Rated cable(line) charging breaking current A

50 and 10

50/10

11 Cable charge breaking current in earthing fault A 20 20 20
12 Rated withstand current (peak) kA 80 63 63
13 Short-time withstand current (2s) kA 25 20 20
14 Mechanism life times 5000 2000 2000

Note: For short circuit breaking and the peak current is based on Fuse plus combination

IEC Fully Insulated 36KV 1250A RMU SF6 GIS SwitchgearIEC Fully Insulated 36KV 1250A RMU SF6 GIS SwitchgearIEC Fully Insulated 36KV 1250A RMU SF6 GIS SwitchgearIEC Fully Insulated 36KV 1250A RMU SF6 GIS Switchgear

Inquiry Cart 0