Knkong Electric Co.,Ltd

Knkong Electric Co.,Ltd

Manufacturer from China
Active Member
5 Years
Home / Products / Gas Insulated Switchgear /

SF6 Metal Clad Gas Insulated Switchgear 36KV MV GIS Electrical Equipment

Contact Now
Knkong Electric Co.,Ltd
City:zhengzhou
Province/State:henan
Country/Region:china
Contact Person:MrKen Chan (English)
Contact Now

SF6 Metal Clad Gas Insulated Switchgear 36KV MV GIS Electrical Equipment

Ask Latest Price
Video Channel
Brand Name :Knkong
Model Number :SF6 GIS HXGN-40.5
Certification :IEC ISO GB
Place of Origin :China
MOQ :1
Payment Terms :L/C, T/T
Supply Ability :100 Unit per month
Delivery Time :30 days
Packaging Details :Standard export packaging
Using Voltage :36KV
Using Current :1250A
Using Frequency :50/60Hz
Original :China
OEM/ODM :Available
Type :Fully insulated
more
Contact Now

Add to Cart

View Product Description

SF6 metal-clad gas-insulated switchgear 36KV MV GIS electrical equipment

Voltage: 36KV

Current: 1250A

Type: Metal-clad SF6 fully insulated

General

The F-unit unit is a fuse switch unit, which is a two-position load switch.
The equipment unit and load switch farm load switch fuse combination.
The grounding switch adopts a dual-mode and grounding on both sides of the fuse at the same time, so as to ensure that the fuse is not charged at the same time except that the grounding switch is closed. The double grounding switch adopts a mechanical interlock, and the primary grounding operates the grounding of the two grounding switches at the same time.

Technical Data

No. Item Unit Parameter
1 Rated voltage kV 12 24 36
2 Rated frequency Hz 50/60
3 Rated current A 630(1250*)
4

1min Power frequency

withstand voltage

wet kV 38 50 70
dry kV 48 60 85
5 Lightning impulse withstand voltage kV 75 125/150 170
6 Rated short circuit breaking current (peak) kA 80 63 63
7 Rated active load and close circuit breaking current A 63 50 50
8 Rated transferring current A 1700 1200 1200
9 Rated short circuit making a current (peak) kA 80 63 63
10 Rated cable(line) charging breaking current A

50 and 10

50/10

11 Cable charge breaking current in earthing fault A 20 20 20
12 Rated withstand current (peak) kA 80 63 63
13 Short-time withstand current (2s) kA 25 20 20
14 Mechanism life times 5000 2000 2000

SF6 Metal Clad Gas Insulated Switchgear 36KV MV GIS Electrical Equipment

Inquiry Cart 0