Fixed type indoor panel use 24KV vacuum circuit breaker 310mm phase spacing
Voltage: 12-24KV
Current: 630-2000A
Breaking current: 20KA
Phase spacing: 310mm
Product overview
Technical Parameters
| No. | Item | Unit | Parameter | ||||||
| 1 | Rated voltage | KV | 12 | ||||||
| 2 | Rated frequency | Hz | 50/60 | ||||||
| 3 | 
			 
 Rated insulation level  | 
			1min power frequency withstand voltage(r. m. s) | 
			 
 KV  | 
			
			 42(phase-to-phase, phase-to-earth) 48(across the isolating distance)  | 
		|||||
| Lighting impulse withstand voltage (peak) | 
			 75(phase-to-phase, phase-to-earth) 85(across the isolating distance)  | 
		||||||||
| 
			 
 
 4  | 
			
			 
 
 Rated current  | 
			
			 
 
 A  | 
			630 | 630 | 1250 | 1600 | |||
| 1250 | 1250 | 1600 | 2000 | ||||||
| 2000 | 2500 | ||||||||
| 2500 | 3150 | ||||||||
| 4000 | |||||||||
| 5 | Rated short-circuit breaking current | 
			 
 KA  | 
			20 | 25 | 31.5 | 40 | |||
| 6 | Rated short-time withstand current | 20 | 25 | 31.5 | 40 | ||||
| 7 | Rated short-circuit marking current | 50 | 63 | 80 | 100 | ||||
| 8 | Rated peak withstand current | 50 | 63 | 80 | 100 | ||||
| 9 | Rated duration of short-circuit | s | 4 | ||||||
| 10 | Rated operating sequence | O-0.3s-O/C-180s-O/C | |||||||
| 11 | Breaking times of rated short-circuit current | Times | 30/20 times(40KA) | ||||||
| 12 | Mechanical endurance | Ops | 20000 | ||||||
| 13 | Rated single capacitor bank breaking current | 
			 
 A  | 
			630 | ||||||
| 14 | Rated back-to-back capacitor bank breaking current | 400 | |||||||
| 15 | Double-earth fault breaking current | 27.4 | |||||||
| 16 | Allowable maximum contact erosion | 
			 
 mm  | 
			3 | ||||||
| 17 | Clearance between open contacts | 10±1 | |||||||
| 18 | Over stroke | 3.5±0.5 | |||||||
| 19 | Non-simultaneity of 3-phase opening and closing | 
			 ms 
  | 
			≤2 | ||||||
| 20 | Bounce duration of contact closing | ≤2 | |||||||
| 21 | Average breaking speed (instant breaking 6mm) | 
			 m/s 
  | 
			1.1±0.2 | ||||||
| 22 | Average making speed | 0.8±0.2 | |||||||
| 23 | Making time | 
			 ms 
  | 
			≤100 | ||||||
| 24 | Breaking time | ≤50 | |||||||
| 
			 
 
 25  | 
			
			 
 Resistance of each phase main circuit  | 
			
			 
 μ Ω  | 
			630A | ≤50 | |||||
| 1250A | ≤45 | ||||||||
| 1600A~2000A | ≤35 | ||||||||
| ≥2500A | ≤25 | ||||||||
| 26 | Contact breaking bounce amplitude | mm | ≤2 | ||||||
| 
			 
 27  | 
			Rated operating voltage | Rated operating voltage(V)AC/DC | 
			 
 V  | 
			24* | 110 | 220 | |||
| Scope of normal operation voltage | Opening:65%-120% rated voltage, in case the voltage is lower than 30% rated voltage, opening operation is not allowed | ||||||||
| 28 | Rated voltage of energy storage motor | V | AC110/220,DC110/220 | ||||||
| 29 | Energy storage time | S | ≤15 | ||||||