Knkong Electric Co.,Ltd

Knkong Electric Co.,Ltd

Manufacturer from China
Active Member
5 Years
Home / Products / VCB Circuit Breaker /

Three Phase HV VCB 40.5 KV Indoor Vacuum Circuit Breaker

Contact Now
Knkong Electric Co.,Ltd
City:zhengzhou
Province/State:henan
Country/Region:china
Contact Person:MrKen Chan (English)
Contact Now

Three Phase HV VCB 40.5 KV Indoor Vacuum Circuit Breaker

Ask Latest Price
Video Channel
Brand Name :Knkong
Model Number :VS1-40.5/E
Certification :CCC,ISO9001,CE, CB,IEC60898
Place of Origin :China
MOQ :1
Price :USD 1000-3000
Payment Terms :L/C, T/T
Supply Ability :100 Unit per month
Delivery Time :30 days
Packaging Details :Standard export packaging
Rated Voltage :40.5 KV
Rated Current :630-2500A
Rated Frequency :50/60Hz
StandArds :ISO IEC GB
Manufactory :KNKONG
OEM/ODM :Available
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Indoor H.V. VCB VS1-40.512-40.5KV,three-phase 50HZ 400/630A, AC/DC 110/220V CCC,ISO9001,CE, CB,IEC60898

Product Introduction

VS1-40.5/T type indoor high voltage vacuum circuit breaker is used for switchgear KYN61-40.5(Z). It's the newest type of power supply and distribution equipment. This product is in accordance with GB1984-2003 standard.

Structure Features

This kind of VCB adopts an integrated design and is different from open-type vacuum circuit breaker and insulation vacuum circuit breaker.
1. The vacuum interrupter and conductive circuit fitting with ring raise resin through the special craft are sealed into a pole.
2. Then with the modularized circuit assembled in a modular circuit breaker.
3. This kind of VCB with excellent electrical&mechanical properties the advanced level of the vacuum circuit breaker in the modern world.

Normal service condition

1. Ambient temperature: -15℃ +40℃, the average temperature is not more than 35℃ in 24 hours
2. Height above sea level:≤1000m;
3. Relative humidity: the average humidity of a day should be no more than 95%; the average humidity of a month should be no more than 90%;
4. Saturated vapor pressure: the average pressure of a day should be no more than 2. 2kPa, the average humidity of a month should be no more than l.8kPa;
5. Environmental conditions: It should be installed in places without dust, smoke, chemical erosion, combustible gas, and saline fume pollution.

VS1-40.5/E Technical Parameters

No. Item Unit Parameter
1 Rated voltage KV 40.5
2 Rated frequency Hz 50
3 Rated power frequency withstand voltage/1 min KV 95
4 Rated lightning impulse withstand voltage KV 185
5 Rated current A 630 1250 1600 2000 2500
6 Rated short-circuit breaking current KA 20 25 31.5
7 Rated short-time withstand current KA 20 25 31.5
8 Rated short-circuit marking current KA 50 63 80
9 Rated peak value of withstanding current KA 50 63 80
10 Rated duration of short-circuit s 4
11 Rated operating sequence O-0.3s-CO-180s-CO
12 Breaking time ms ≤80
13 Mechanical endurance times 10000
14 Rated single capacitor bank breaking current A 400/630
15 Rated short circuit breaking current breaking times times 30
16 Size (length*width*high) mm 1246*1700*905
17 Rated voltage of energy storage motor V AC110/220, DC110/220
18 Weight Kg 466

Mechanical Properties Parameters

No. Item Unit Parameter
1 Clearance between open contacts mm 18±2
2 Over stroke 3.5~4
3 Rated power of energy storage motor W 230
4 Energy storage time s ≤15
5 Bounce duration of contact closing

ms

≤3
6 Non-simultaneity of 3-phase opening and closing ≤2
7 Breaking time ≤70
8 Making time ≤90
9 Break-brake bounce m ≤3
10 Average breaking speed m/s 1.7±0.3
11 Average making speed 0.7±0.3

Three Phase HV VCB 40.5 KV Indoor Vacuum Circuit BreakerThree Phase HV VCB 40.5 KV Indoor Vacuum Circuit BreakerThree Phase HV VCB 40.5 KV Indoor Vacuum Circuit Breaker

Inquiry Cart 0