Shenzhen Dong Sheng Yuan Electrical Equipment Co., Ltd.

quality first, reputation-based, and excellent service

Manufacturer from China
Verified Supplier
1 Years
Home / Products / Box Type Substation /

10kV Electric Distribution Substation Ring Network Box IP56 Protection

Contact Now
Shenzhen Dong Sheng Yuan Electrical Equipment Co., Ltd.
Visit Website
City:shenzhen
Country/Region:china
Contact Person:MrLeo
Contact Now

10kV Electric Distribution Substation Ring Network Box IP56 Protection

Ask Latest Price
Video Channel
Brand Name :Dong Sheng Yuan
Model Number :10kV Primary And Secondary Integrated Equipment (ring Network Box)
Place of Origin :Zhuhai, China
Delivery Time :T+30
Payment Terms :TT
Shape :Rectangle
Protection Level :IP56
Frequency :50/60Hz,50Hz or 60Hz
Rated Voltage :10kV
Usage :Power,Distribution
Item :prefabricated substation
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Basic Info.

Model NO.
European substation

Form
Partly-welded Type
Operation Voltage
High Voltage
Size
3 Uint
Application Range
Power Plants
Shell Material
Stainless Steel
Shell Protection Grade
IP56
Brand
DSY
Transport Package
Customized
Specification
customized
Trademark
DSY
Origin
China, Zhuhai
Production Capacity
3000

Packaging & Delivery

Package Size
1750.00cm * 1600.00cm * 2200.00cm
Package Gross Weight
460.000kg

Product Description

Transformer technical parameters table
Product Description

Main technical parameter

Preassembled substation technical parameter table

Serial number Name Unit Technical specification
1 rated voltage KV 10/0.4(high voltage/low voltage)
2 maximum working voltage KV 12(high-pressure side)
3 rated frequency HZ 50
4 rated capacity KVA 50-1600
5 1-minute power frequency withstand voltage KV 35
6 lightning impulse voltage KV 75
7 type of cooling
Oil immersed in self-cooling
8 High voltage backup fuse breaking current KA 50
9 Breaking the current of the plug-in fuse KA 2.5
10 environment temperature ºC -35~+40
11 Coil allowable temperature rise ºC 65
12 No load voltage regulation
±5%or±2x2.5%
13 noise grade db 50
14 level of protection
IP43


Transformer technical parameters table

Selection of new S9 series transformer body, low loss, good overload capacity, strong short-circuit resistance, all fasteners are anti-loose treatment, no lifting core; S10 series and S11 series transformers with better performance are also available.
Capacity kva Voltage no-load current open circuit losses impedance voltage load loss
high voltage low voltage S9 S10 S11 S9 S10 S11 4.0 S9 S10 S11
50 10±5%
±2x2.5%
0.4 2.0 1.9 0.75 0.17 0.15 0.12 0.87 0.83 0.87
63 1.9 1.8 0.7 0.2 0.18 0.14 1.04 0.99 1.04
80 1.9 1.7 0.7 0.25 0.22 0.175 1.25 1.2 1.25
100 1.8 1.55 0.65 0.29 0.26 0.2 1.5 1.42 1.5
125 1.7 1.45 0.65 0.34 0.3 0.235 1.8 1.72 1.8
160 1.6 1.3 0.6 0.4 0.36 0.27 2.2 2.12 2.2
200 1.5 1.2 0.55 0.48 0.43 0.33 2.6 2.5 2.6
250 1.4 1.1 0.5 0.56 0.5 0.39 3.05 2.9 3.05
315 1.4 1.0 0.45 0.67 0.29 0.465 3.65 3.45 3.65
400 1.3 1.0 0.4 0.8 0.71 0.56 4.3 4.15 4.3
500 1.2 1.0 0.4 0.96 0.85 0.67 5.15 4.82 5.15
630 1.1 0.8 0.4 1.2 1.6 0.81 4.5 6.2 5.86 6.2
800 1.0 0.7 0.35 1.4 1.23 0.98 7.5 7.2 7.5
1000 1.0 0.6 0.3 1.7 1.5 1.15 10.3 9.8 10.3
1250 0.9 0.6 0.27 1.95 1.72 1.36 12.0 12.2 12.0

main technical parameters

Load switch technical parameter table

The load switch is an oil-immersed, three-phase linkage switch with, spring operating mechanism; It can be operated with load division and brake, and its division and speed have nothing to do with the size of the operating force. There are two stations, four stations T-type, four stations V-type, and so on.

Serial number Name Unit Four-station loop load switch Two-station load switch
1 rated voltage A 630 315
2 Rated short-circuit closing current KA 31.5 31.5
3 rated short-time current KA 12.5 12.5
4 Rated short endurance time S 2 2
5 mechanical life Next 2000 2000
6 Lightning impulse withstand voltage peak full wave Phase to phase KV 75 75
7 isolating fracture
85 85
8 1min power frequency withstand voltage Phase to phase KV 42 42
9 isolating fracture
48 48
10 Rated peak withstand current KA 31.5 31.5

Fuse technical parameters(The company oil oil-immersed fuse selection configuration recommendation table)


Serial number Three-phase transformer capacity(KVA) XRNT rated current(A) PRNT1 Overload protection rated current(A)
1 30 10 6
2 50 16 8
3 80 16 10
4 100 20 15
5 125 25 15
6 160 31.5 25
7 200 40 25
8 250 50 40
9 315 63 40
10 400 63 40
11 500 80 50
12 630 100 50/65
13 800 125 65
14 1250 160 100
15 1600 200 140


Inquiry Cart 0