10kV 12kV Permanent Magnetic Circuit Breaker Switch Three Phase For Smart Grid

Ask Latest Price
Video Channel
Brand Name :Dong Sheng Yuan
Model Number :10kV permanent magnet circuit breaker switch
Place of Origin :Zhuhai, China
Delivery Time :T+30
Payment Terms :TT
Rated voltage :12kV
Rated frequency :50Hz
Ambient temperature range :-40°C to +70°C
Protection Functions :Overload/Short Circuit/Ground Fault
Arc Extinguishing Method :vacuum circuit breaker
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Product Introduction

Product overview


---Outdoor high-voltage fast permanent magnet vacuum circuit breaker is an outdoor distribution vacuum circuit breaker with a rated voltage of 12kV and three-phase AC 50Hz.


---Outdoor high-voltage vacuum circuit breaker is a new generation of outdoor column vacuum circuit breaker developed to meet the needs of the smart grid.


--- It is used to switch loads of different properties and frequent operations, and can break short-circuit current many times.


---It can be used as the 10kV side outgoing line of the main transformer of the substation and the switch on the column of the distribution network.


---It is the preferred equipment to realize the intellectual, automation, and miniaturization of the distribution network.

Technical parameters


Item

Unit

Parameter

Rated voltage

kV

12

Rated current

A

630/1250

Rated frequency

Hz

50

Rated lightning impulse withstand voltage(peak)

kV

ground 75/fracture 85

Rated short-time power frequency withstand voltage(1min)

kV

wet test 34/ dry test 42/ fracture 48

Rated short-circuit breaking current

kA

25

Rated short-circuit breaking current times

Times

30

Rated short-time withstand current

kV

25

Rated short circuit duration

s

4

Rated peak withstand current

kA

50

Rated short-circuit making current

kA

50

Power frequency withstand voltage of secondary circuit(1min)

kV

2

Rated operating sequence


O-0.3s-CO-180S-CO

Mechanical life

Times

30000

Working conditions


1. Ambient air temperature: upper limit + 70 ºC, lower limit - 40 ºC


2. Air relative humidity: the daily average value shall not be greater than 95%, and the monthly average value shall not be greater than 90%;


3. Altitude: < 2000m;


4. Wind pressure: no more than 700pa (equivalent to wind speed of 34m / s)


5. Pollution level: Class V (specific creepage distance ≥ 31mm / kV)


6. Icing thickness: ≤ 10mm;


7. Seismic intensity: ≤ 8 degrees;


8. Installation site: there shall be no fire, explosion hazard, serious pollution, chemical corrosion, or violent vibration.

Main Functions


1. protection: it is equipped with three-stage voltage blocking directional overcurrent protection, inverse time overcurrent protection, zero sequence protection, acceleration protection, overload protection, low-frequency load shedding, low-voltage splitting, and three-phase triple reclosing;


2. Measurement: three-phase voltage, current, power factor, frequency, etc.


3. control function: automatic reclosing, local control, and remote control can be set


4. Communication function: standard RS232, RS485, or Ethernet interface, supporting optical fiber, distribution network carrier, wireless, twisted pair, and other communication modes, GPRS short message or communication, etc.


5. Other functions: local display, parameter setting, fault recording and alarm, etc.

Inquiry Cart 0